Connect Tech CPU Servisní příručka Strana 530

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 650
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 529
Technology DBs
CPU 317T: Technology Functions
7-58 A5E00251798-03
7.11.7 ErrorIDs - MCDevice / Trace technology DB
Valid for firmware version V3.1.x of the integrated technology
Error
ErrorID
Error message Possible causes To correct or avoid errors Interrupts in
S7T Config*
8008 Invalid technology DB
(unknown GuID or
InstanzID)
The technology does not
recognize this DB, because
it has an invalid internal ID.
The DB may have been
generated in a copy
operation.
Recreate the DB in the
"Technology Objects
Management" dialog box, and
download the configuration data
again, i.e. establish online /
offline consistency.
8009 The technology DB is
disabled because it was
substituted with a new
instance
The DB is no longer
assigned to the technology
object, because a newer
instance with a different DB
number has been
downloaded.
Delete the DB
* Interrupts in S7T Config, which may be associated with the indicated error.
Zobrazit stránku 529